D121350D

AGM Deep Cycle Cyclic Battery

Discover® VRLA AGM Deep Cycle batteries deliver deep-cycle and cyclic discharging for a general range of stationary applications such as backup power, solar, and renewable energy storage. The batteries are maintenance-free, safe, easy to use and a start to reducing energy cost and grid dependence.

MECHANICAL SPECIFICATIONS
Industry Reference   
Length A (in/mm) 13.4 341
Width B (in/mm) 6.8 173
Height C (in/mm) 11.1 283
Total Height D (in/mm) 11.3 288
Weight (lbs/kgs) 90 41
Terminal * F12M8
Technology AGM, VRLA

NOTE 1: Dimensions have a ±2 mm (0.08 in) tolerance. Weights may vary.
NOTE 2: Refer to terminal guide on website for torque values.

ELECTRICAL SPECIFICATIONS
Voltage (V) 12
Internal Resistance (mΩ) 5
Short Circuit (A) (20°C / 68°F) 2400
Self-Discharge (20°C / 68°F) 2-3% per month
Charge Temperature Min: -10°C (14°F) | Max: 50°C (122°F)
Discharge Temperature Min: -40°C (-40°F) | Max: 50°C (122°F)
Storage Temperature -20°C (-4°F) to 60°C (140°F)

NOTE 3: Extra considerations must be given when designing systems for use at maximum temperatures.
NOTE 4: Internal Resistance is approximate.

PERFORMANCE SPECIFICATIONS
Amp Hours (AH)
1 HR 5 HR 10 HR 20 HR
92 120 135 140

1HR @1.60VPC, 5HR @1.75VPC; 10 HR@ 1.80VPC; 20 HR @1.80VPC. All at 30°C/86°F

Discharge Constant Current (Amperes) @ 25°C / 77°F
VPC/Time 5 MIN 10 MIN 15 MIN 30 MIN 1 HR 3 HR 5 HR 10 HR 20 HR
1.60 VPC 440.00 310.00 245.00 152.00 92.00 39.50 25.30 13.90 7.20
1.65 VPC 423.00 297.00 236.00 147.00 89.00 38.60 25.00 13.90 7.20
1.70 VPC 404.00 283.00 226.00 142.00 85.50 37.50 24.60 13.80 7.15
1.75 VPC 383.00 267.00 216.00 136.00 82.00 36.40 24.20 13.70 7.10
1.80 VPC 361.00 249.00 205.00 129.00 78.00 35.20 23.70 13.50 7.00

 

Discharge Constant Power (Watts) @ 25°C / 77°F
VPC/Time 5 MIN 10 MIN 15 MIN 30 MIN 1 HR 3 HR 5 HR 10 HR 20 HR
1.60 VPC 760.00 550.00 480.00 285.00 175.00 72.00 51.00
1.65 VPC 730.00 525.00 460.00 273.00 170.00 70.50 50.20
1.70 VPC 697.00 498.00 439.00 259.00 164.00 68.80 49.30
1.75 VPC 660.00 468.00 417.00 245.00 158.00 67.00 48.30
1.80 VPC 620.00 435.00 393.00 230.00 151.00 65.00 47.10
image.png
no garbage datasheet icon
recycle icon datasheet icon
ce certification datasheet icon
recognized component mark datasheet icon
iata icao certification datasheet icon
iso din certification datasheet icon
 
BENEFITS

ENHANCED RUNTIME

  • High energy density
  • Consistent voltage performance

EXTENDED SERVICE LIFE

  • Low self-discharge rates prolongs shelf life
  • 99% gas recombination extends life
  • Long life superior to general purpose batteries

EXTREME TEMPERATURES

  • Wide ambient operating temperature
  • Low temperature operation superior to FLA / Gel batteries

RELIABLE AND SAFE

  • Valve Regulated Lead-Acid, AGM
  • Maintenance-free, nonspillable, no-gassing
  • Flame retardant (UL94:V0) ABS case and cover available

CERTIFIED QUALITY

Discover® manufacturing facilities are fully certified to ISO 9001/14001 and OSHA 18001 standards.

Designed in accordance with and published in compliance with applicable standards, including:

  • IEC 60896-21/22
  • BS EN 60254-1:2005
  • UL, CE Health Safety Certified
SHIPPING CLASSIFICATION
  • Classified as a nonspillable battery
  • Without restriction for transport by Sea (IMDG amendment 27)
  • Without restriction for transport by Air (IATA/ICAO provision 67)
  • Without restriction for transport by Ground (STB, DOT-CFR-HMR49)
 
 
Cycle Life Characteristics
gra vrla deep cycle cycle life characteristics
Temperature Effects on Capacity
gra vrla deep cycle temperature effects on capacity
Charge Characteristics
gra vrla deep cycle charge characteristics
Discharge Characteristics
gra vrla deep cycle discharge characteristics
  1. Due to self-discharge characteristics of lead acid battery technologies, batteries should be charged within 6 months of storage to ensure optimum performance, prevent sulphation and permanent capacity loss.
  2. Charge profile recommendations correspond to battery voltages at 25°C (77°F). For temperatures below, adjust +5mVPC/°C (+3mVPC/°F). Temperatures above, adjust -5mVPC/°C (-3mVPC/°F). Temperature compensated charging helps ensure optimum battery runtime and life performance.
  3. Charge until battery voltage reaches 2.45VPC and hold until current tapers down to 0.01C20 amps. Battery is fully charged under these conditions and charger should be disconnected or switched to “float” voltage. For standby / float use, a constant charge voltage of 2.25-2.30VPC is also acceptable. Hold until the battery seeks its own current level and maintain itself in a fully charged condition.

D121350D

Printed: 28/03/2024

AGM Deep Cycle Cyclic Battery

Discover® VRLA AGM Deep Cycle batteries deliver deep-cycle and cyclic discharging for a general range of stationary applications such as backup power, solar, and renewable energy storage. The batteries are maintenance-free, safe, easy to use and a start to reducing energy cost and grid dependence.

BENEFITS

ENHANCED RUNTIME

  • High energy density
  • Consistent voltage performance

EXTENDED SERVICE LIFE

  • Low self-discharge rates prolongs shelf life
  • 99% gas recombination extends life
  • Long life superior to general purpose batteries

EXTREME TEMPERATURES

  • Wide ambient operating temperature
  • Low temperature operation superior to FLA / Gel batteries

RELIABLE AND SAFE

  • Valve Regulated Lead-Acid, AGM
  • Maintenance-free, nonspillable, no-gassing
  • Flame retardant (UL94:V0) ABS case and cover available

CERTIFIED QUALITY

Discover® manufacturing facilities are fully certified to ISO 9001/14001 and OSHA 18001 standards.

Designed in accordance with and published in compliance with applicable standards, including:

  • IEC 60896-21/22
  • BS EN 60254-1:2005
  • UL, CE Health Safety Certified
SHIPPING CLASSIFICATION
  • Classified as a nonspillable battery
  • Without restriction for transport by Sea (IMDG amendment 27)
  • Without restriction for transport by Air (IATA/ICAO provision 67)
  • Without restriction for transport by Ground (STB, DOT-CFR-HMR49)
MECHANICAL SPECIFICATIONS
Industry Reference   
Length A (in/mm) 13.4 341
Width B (in/mm) 6.8 173
Height C (in/mm) 11.1 283
Total Height D (in/mm) 11.3 288
Weight (lbs/kgs) 90 41
Terminal * F12M8
Technology AGM, VRLA

NOTE 1: Dimensions have a ±2 mm (0.08 in) tolerance. Weights may vary.
NOTE 2: Refer to terminal guide on website for torque values.

ELECTRICAL SPECIFICATIONS
Voltage (V) 12
Internal Resistance (mΩ) 5
Short Circuit (A) (20°C / 68°F) 2400
Self-Discharge (20°C / 68°F) 2-3% per month
Charge Temperature Min: -10°C (14°F) | Max: 50°C (122°F)
Discharge Temperature Min: -40°C (-40°F) | Max: 50°C (122°F)
Storage Temperature -20°C (-4°F) to 60°C (140°F)

NOTE 3: Extra considerations must be given when designing systems for use at maximum temperatures.
NOTE 4: Internal Resistance is approximate.

image.png
no garbage datasheet icon
recycle icon datasheet icon
ce certification datasheet icon
recognized component mark datasheet icon
iata icao certification datasheet icon
iso din certification datasheet icon
 
PERFORMANCE SPECIFICATIONS
Amp Hours (AH)
1 HR 5 HR 10 HR 20 HR
92 120 135 140

1HR @1.60VPC, 5HR @1.75VPC; 10 HR@ 1.80VPC; 20 HR @1.80VPC. All at 30°C/86°F

PERFORMANCE SPECIFICATIONS
Discharge Constant Current (Amperes) @ 25°C / 77°F
VPC/Time 5 MIN 10 MIN 15 MIN 30 MIN 1 HR 3 HR 5 HR 10 HR 20 HR
1.60 VPC 440.00 310.00 245.00 152.00 92.00 39.50 25.30 13.90 7.20
1.65 VPC 423.00 297.00 236.00 147.00 89.00 38.60 25.00 13.90 7.20
1.70 VPC 404.00 283.00 226.00 142.00 85.50 37.50 24.60 13.80 7.15
1.75 VPC 383.00 267.00 216.00 136.00 82.00 36.40 24.20 13.70 7.10
1.80 VPC 361.00 249.00 205.00 129.00 78.00 35.20 23.70 13.50 7.00

15MIN @1.67 VPC; 1HR @1.60VPC, 5HR @1.75VPC; 10 HR@ 1.80VPC; 20 HR @1.80VPC. All at 30°C/86°F

 
Discharge Constant Power (Watts) @ 25°C / 77°F
VPC/Time 5 MIN 10 MIN 15 MIN 30 MIN 1 HR 3 HR 5 HR 10 HR 20 HR
1.60 VPC 760.00 550.00 480.00 285.00 175.00 72.00 51.00
1.65 VPC 730.00 525.00 460.00 273.00 170.00 70.50 50.20
1.70 VPC 697.00 498.00 439.00 259.00 164.00 68.80 49.30
1.75 VPC 660.00 468.00 417.00 245.00 158.00 67.00 48.30
1.80 VPC 620.00 435.00 393.00 230.00 151.00 65.00 47.10
Cycle Life Characteristics
gra vrla deep cycle cycle life characteristics
Temperature Effects on Capacity
gra vrla deep cycle temperature effects on capacity
Charge Characteristics
gra vrla deep cycle charge characteristics
Discharge Characteristics
gra vrla deep cycle discharge characteristics
  1. Due to self-discharge characteristics of lead acid battery technologies, batteries should be charged within 6 months of storage to ensure optimum performance, prevent sulphation and permanent capacity loss.
  2. Charge profile recommendations correspond to battery voltages at 25°C (77°F). For temperatures below, adjust +5mVPC/°C (+3mVPC/°F). Temperatures above, adjust -5mVPC/°C (-3mVPC/°F). Temperature compensated charging helps ensure optimum battery runtime and life performance.
  3. Charge until battery voltage reaches 2.45VPC and hold until current tapers down to 0.01C20 amps. Battery is fully charged under these conditions and charger should be disconnected or switched to “float” voltage. For standby / float use, a constant charge voltage of 2.25-2.30VPC is also acceptable. Hold until the battery seeks its own current level and maintain itself in a fully charged condition.
Related Resources
Related Resources