D12180

AGM Float Standby Battery

Discover® VRLA AGM Float Standby batteries deliver high reliability in general purpose applications to avoid disruptions in life and productivity. The batteries are maintenance-free and the ideal solution for medical devices, security systems and emergency lighting, among other applications.

MECHANICAL SPECIFICATIONS
Industry Reference   
Length A (in/mm) 7.1 181
Width B (in/mm) 3 77
Height C (in/mm) 6.6 167
Total Height D (in/mm) 6.6 167
Weight (lbs/kgs) 11.2 5.1
Terminal * F13M5
Technology AGM, VRLA

NOTE 1: Dimensions have a ±2 mm (0.08 in) tolerance. Weights may vary.
NOTE 2: Refer to terminal guide on website for torque values.

ELECTRICAL SPECIFICATIONS
Voltage (V) 12
Internal Resistance (mΩ) 23
Short Circuit (A) (20°C / 68°F) 500
Self-Discharge (20°C / 68°F) 2-3% per month
Charge Temperature Min: -10°C (14°F) | Max: 50°C (122°F)
Discharge Temperature Min: -40°C (-40°F) | Max: 50°C (122°F)
Storage Temperature -20°C (-4°F) to 60°C (140°F)

NOTE 3: Extra considerations must be given when designing systems for use at maximum temperatures.
NOTE 4: Internal Resistance is approximate.

PERFORMANCE SPECIFICATIONS
Amp Hours (AH)
1 HR 5 HR 10 HR 20 HR
11 15 16 18

1HR @1.60VPC, 5HR @1.75VPC; 10 HR@ 1.80VPC; 20 HR @1.80VPC. All at 30°C/86°F

Discharge Constant Current (Amperes) @ 25°C / 77°F
VPC/Time 5 MIN 10 MIN 15 MIN 30 MIN 1 HR 3 HR 5 HR 10 HR 20 HR
1.60 VPC 63.70 42.80 32.60 19.20 11.00 4.49 3.05 1.70 0.95
1.65 VPC 61.40 41.80 31.80 18.80 10.70 4.40 3.00 1.68 0.94
1.70 VPC 59.10 40.80 31.00 18.40 10.40 4.30 2.95 1.66 0.93
1.75 VPC 56.80 39.60 30.20 18.00 10.00 4.21 2.90 1.64 0.91
1.80 VPC 54.50 38.60 29.40 17.50 9.70 4.12 2.85 1.62 0.90

 

Discharge Constant Power (Watts) @ 25°C / 77°F
VPC/Time 5 MIN 10 MIN 15 MIN 30 MIN 1 HR 3 HR 5 HR 10 HR 20 HR
1.60 VPC 129.00 81.70 64.90 38.00 22.40 10.50 6.57
1.65 VPC 125.00 79.20 63.40 36.80 21.50 9.84 6.57
1.70 VPC 120.00 76.00 60.80 35.60 20.40 9.09 6.24
1.75 VPC 113.00 72.70 58.30 34.30 19.30 8.29 5.89
1.80 VPC 107.00 69.30 56.00 32.90 18.00 7.38 5.46
image.png
no garbage datasheet icon
recycle icon datasheet icon
ce certification datasheet icon
recognized component mark datasheet icon
iata icao certification datasheet icon
iso din certification datasheet icon
 
BENEFITS

EXTENDED SERVICE LIFE

  • Up to 5 year design life
  • Low self-discharge rates prolongs shelf life
  • 99% gas recombination extends life

EXTREME TEMPERATURES

  • Wide ambient operating temperature
  • Low temperature operation superior to FLA / Gel batteries

RELIABLE AND SAFE

  • Valve Regulated Lead-Acid, AGM
  • Maintenance-free, nonspillable, no-gassing
  • Flame retardant (UL94:V0) ABS case and cover available

CERTIFIED QUALITY

Discover® manufacturing facilities are fully certified to ISO 9001/14001 and OSHA 18001 standards.

Designed in accordance with and published in compliance with applicable standards, including:

  • IEC 60896-21/22
  • BS EN 60254-1:2005
  • UL, CE Health Safety Certified
SHIPPING CLASSIFICATION
  • Classified as a nonspillable battery
  • Without restriction for transport by Sea (IMDG amendment 27)
  • Without restriction for transport by Air (IATA/ICAO provision 67)
  • Without restriction for transport by Ground (STB, DOT-CFR-HMR49)
 
 
Temperature Effects on Float Life
gra vrla float standby temperature effects on float life
Temperature Effects on Capacity
gra vrla float standby temperature effects on capacity
Charge Characteristics (Cyclic)
gra vrla float standby charge characteristics
Discharge Characteristics
gra vrla float standby discharge characteristics
Self-Discharge Characteristics
gra vrla float standby self discharge characteristics
  1. Due to self-discharge characteristics of lead acid battery technologies, batteries should be charged within 6 months of storage to ensure optimum performance, prevent sulphation and permanent capacity loss.
  2. Charge profile recommendations correspond to battery voltages at 25°C (77°F). For temperatures below, adjust +5mVPC/°C (+3mVPC/°F). Temperatures above, adjust -5mVPC/°C (-3mVPC/°F). Temperature compensated charging helps ensure optimum battery runtime and life performance.
  3. Charge until battery voltage reaches 2.45VPC and hold until current tapers down to 0.01C20 amps. Battery is fully charged under these conditions and charger should be disconnected or switched to “float” voltage. For standby / float use, a constant charge voltage of 2.25-2.30VPC is also acceptable. Hold until the battery seeks its own current level and maintain itself in a fully charged condition.

D12180

Printed: 13/10/2024

AGM Float Standby Battery

Discover® VRLA AGM Float Standby batteries deliver high reliability in general purpose applications to avoid disruptions in life and productivity. The batteries are maintenance-free and the ideal solution for medical devices, security systems and emergency lighting, among other applications.

BENEFITS

EXTENDED SERVICE LIFE

  • Up to 5 year design life
  • Low self-discharge rates prolongs shelf life
  • 99% gas recombination extends life

EXTREME TEMPERATURES

  • Wide ambient operating temperature
  • Low temperature operation superior to FLA / Gel batteries

RELIABLE AND SAFE

  • Valve Regulated Lead-Acid, AGM
  • Maintenance-free, nonspillable, no-gassing
  • Flame retardant (UL94:V0) ABS case and cover available

CERTIFIED QUALITY

Discover® manufacturing facilities are fully certified to ISO 9001/14001 and OSHA 18001 standards.

Designed in accordance with and published in compliance with applicable standards, including:

  • IEC 60896-21/22
  • BS EN 60254-1:2005
  • UL, CE Health Safety Certified
SHIPPING CLASSIFICATION
  • Classified as a nonspillable battery
  • Without restriction for transport by Sea (IMDG amendment 27)
  • Without restriction for transport by Air (IATA/ICAO provision 67)
  • Without restriction for transport by Ground (STB, DOT-CFR-HMR49)
MECHANICAL SPECIFICATIONS
Industry Reference   
Length A (in/mm) 7.1 181
Width B (in/mm) 3 77
Height C (in/mm) 6.6 167
Total Height D (in/mm) 6.6 167
Weight (lbs/kgs) 11.2 5.1
Terminal * F13M5
Technology AGM, VRLA

NOTE 1: Dimensions have a ±2 mm (0.08 in) tolerance. Weights may vary.
NOTE 2: Refer to terminal guide on website for torque values.

ELECTRICAL SPECIFICATIONS
Voltage (V) 12
Internal Resistance (mΩ) 23
Short Circuit (A) (20°C / 68°F) 500
Self-Discharge (20°C / 68°F) 2-3% per month
Charge Temperature Min: -10°C (14°F) | Max: 50°C (122°F)
Discharge Temperature Min: -40°C (-40°F) | Max: 50°C (122°F)
Storage Temperature -20°C (-4°F) to 60°C (140°F)

NOTE 3: Extra considerations must be given when designing systems for use at maximum temperatures.
NOTE 4: Internal Resistance is approximate.

image.png
no garbage datasheet icon
recycle icon datasheet icon
ce certification datasheet icon
recognized component mark datasheet icon
iata icao certification datasheet icon
iso din certification datasheet icon
 
PERFORMANCE SPECIFICATIONS
Amp Hours (AH)
1 HR 5 HR 10 HR 20 HR
11 15 16 18

1HR @1.60VPC, 5HR @1.75VPC; 10 HR@ 1.80VPC; 20 HR @1.80VPC. All at 30°C/86°F

PERFORMANCE SPECIFICATIONS
Discharge Constant Current (Amperes) @ 25°C / 77°F
VPC/Time 5 MIN 10 MIN 15 MIN 30 MIN 1 HR 3 HR 5 HR 10 HR 20 HR
1.60 VPC 63.70 42.80 32.60 19.20 11.00 4.49 3.05 1.70 0.95
1.65 VPC 61.40 41.80 31.80 18.80 10.70 4.40 3.00 1.68 0.94
1.70 VPC 59.10 40.80 31.00 18.40 10.40 4.30 2.95 1.66 0.93
1.75 VPC 56.80 39.60 30.20 18.00 10.00 4.21 2.90 1.64 0.91
1.80 VPC 54.50 38.60 29.40 17.50 9.70 4.12 2.85 1.62 0.90

15MIN @1.67 VPC; 1HR @1.60VPC, 5HR @1.75VPC; 10 HR@ 1.80VPC; 20 HR @1.80VPC. All at 30°C/86°F

 
Discharge Constant Power (Watts) @ 25°C / 77°F
VPC/Time 5 MIN 10 MIN 15 MIN 30 MIN 1 HR 3 HR 5 HR 10 HR 20 HR
1.60 VPC 129.00 81.70 64.90 38.00 22.40 10.50 6.57
1.65 VPC 125.00 79.20 63.40 36.80 21.50 9.84 6.57
1.70 VPC 120.00 76.00 60.80 35.60 20.40 9.09 6.24
1.75 VPC 113.00 72.70 58.30 34.30 19.30 8.29 5.89
1.80 VPC 107.00 69.30 56.00 32.90 18.00 7.38 5.46
Temperature Effects on Float Life
gra vrla float standby temperature effects on float life
Temperature Effects on Capacity
gra vrla float standby temperature effects on capacity
Charge Characteristics (Cyclic)
gra vrla float standby charge characteristics
Discharge Characteristics
gra vrla float standby discharge characteristics
Self-Discharge Characteristics
gra vrla float standby self discharge characteristics
  1. Due to self-discharge characteristics of lead acid battery technologies, batteries should be charged within 6 months of storage to ensure optimum performance, prevent sulphation and permanent capacity loss.
  2. Charge profile recommendations correspond to battery voltages at 25°C (77°F). For temperatures below, adjust +5mVPC/°C (+3mVPC/°F). Temperatures above, adjust -5mVPC/°C (-3mVPC/°F). Temperature compensated charging helps ensure optimum battery runtime and life performance.
  3. Charge until battery voltage reaches 2.45VPC and hold until current tapers down to 0.01C20 amps. Battery is fully charged under these conditions and charger should be disconnected or switched to “float” voltage. For standby / float use, a constant charge voltage of 2.25-2.30VPC is also acceptable. Hold until the battery seeks its own current level and maintain itself in a fully charged condition.
Related Resources