Battery Testing
Visual inspection alone is insufficient to determine the battery's overall health.
Specific Gravity Test
DO NOT ADD WATER BEFORE TESTING (Flooded batteries only)
- Fill and drain the hydrometer 2 to 4 times before pulling out a sample.
- The hydrometer should have enough sample electrolytes to support the float completely.
- Record a reading, and return the electrolyte to the cell.
- The OCV of the tested cell will be the specific gravity reading + .84
- Example 1.22 s.g. + .84 = 2.06V
- To check another cell, repeat steps 1 thru 3 above.
- Check all cells in the battery.
- Replace the vent caps and wipe off any electrolytes that might have been spilled.
- Correct the readings to 80°F:
- Add .004 to readings for every 10° above 80°F, ( 6o above 26°C)
- Subtract .004 for every 10° below 80°F, ( 6o below 26°C)
- Compare the readings.
- Check the state of charge using “Open Circuit Voltage” table below.
- The OCV of the tested cell will be the specific gravity reading + .84
- Example 1.22 s.g. + .84 = 2.06V
The readings should be at or above the factory specification or 1.280 ± .005. If any specific gravity readings register low, then follow the steps below:
- Check and record voltage level(s).
- Put battery(s) on a complete charge.
- Retake specific gravity readings.
If any specific gravity readings still register low, then follow the steps below:
- Check voltage level(s).
- Perform equalization charge. Refer to the Equalizing section for the proper procedure.
- Retake specific gravity readings.
If any specific gravity reading still registers lower than the factory specification or 1.280 ± .005, then one or more of the following conditions may exist:
- The battery is old and approaching the end of its life.
- The battery was left in a state of discharge for too long.
- The electrolyte was lost due to spillage or overflow.
- A weak or bad cell is developing.
- The battery was overwatered previous to testing.
- Batteries in conditions 1 - 4 should be taken to a specialist for further evaluation or retired from service.
Open-Circuit Voltage Test
For accurate voltage readings, batteries must remain idle (no charging, no discharging) for at least 8 hours, preferably 24 hrs.
- Disconnect all loads from the batteries.
- Test specific gravity if possible. The OCV of the tested cell will be the specific gravity reading + .84 • Example 1.22 s.g. + .84 = 2.06V.
- Measure the voltage using a DC voltmeter.
- Check the state of charge with the Table below.
- Charge the battery if it registers 0% to 75 % charged.
After the charge, if the battery registers below the Temperature Compensated values illustrated in “How can you tell if a battery is fully charged” or “How can I measure my battery's State of Charge,” the following conditions may exist:
- The battery was left in a state of discharge for too long.
- The battery has a bad cell.
Batteries in these conditions should be taken to a specialist for further evaluation or retired from service.
Load Testing
Use this same procedure for VRLA DRY CELL batteries and flooded batteries:
- Recharge if the open circuit voltage is below 75%.
- If you have an adjustable load tester, set the load at 3 to 3.5 times the 20-hour rate.
- Apply the load for 15 seconds. The voltage should stabilize above 9.6 volts while on load.
- If the battery has a CCA rating, you can apply a load equal to ½ the rating for 15 seconds. The voltage should stabilize above 9.6 volts while on load.
- To apply a more determined test, you may apply a load equal to 100% of the rated CCA or 5 to 6 times the 20-hour rate for 30 seconds. The voltage should stabilize above 7.2 volts while on load.
- If below 9.6 volts (7.2 volts for the 100% CCA test), recharge and repeat the test. If below 9.6 volts (7.2 volts for the 100% CCA test) again, replace the battery.
Specific Gravity Test
DO NOT ADD WATER BEFORE TESTING (Flooded batteries only)
- Fill and drain the hydrometer 2 to 4 times before pulling out a sample.
- The hydrometer should have enough sample electrolytes to support the float completely.
- Record a reading, and return the electrolyte to the cell.
- The OCV of the tested cell will be the specific gravity reading + .84
- Example 1.22 s.g. + .84 = 2.06V
- To check another cell, repeat steps 1 thru 3 above.
- Check all cells in the battery.
- Replace the vent caps and wipe off any electrolytes that might have been spilled.
- Correct the readings to 80°F:
- Add .004 to readings for every 10° above 80°F, ( 6° above 26°C)
- Subtract .004 for every 10° below 80°F, ( 6° below 26°C)
- Compare the readings.
Check the state of charge using the “Open Circuit Voltage” table below.
The OCV of the tested cell will be the specific gravity reading + .84
- Example 1.22 s.g. + .84 = 2.06V
The readings should be at or above the factory specification or 1.280 ± .005. If any specific gravity readings register low, then follow the steps below:
- Check and record voltage level(s).
- Put battery(s) on a complete charge.
- Retake specific gravity readings.
If any specific gravity readings still register low, then follow the steps below:
- Check voltage level(s).
- Perform equalization charge. Refer to the Equalizing section for the proper procedure.
- Retake specific gravity readings.
If any specific gravity reading still registers lower than the factory specification or 1.280 ± .005, then one or more of the following conditions may exist:
- The battery is old and approaching the end of its life.
- The battery was left in a state of discharge for too long.
- The electrolyte was lost due to spillage or overflow.
- A weak or bad cell is developing.
- The battery was overwatered previous to testing.
- Batteries in conditions 1 - 4 should be taken to a specialist for further evaluation or retired from service.
Open-Circuit Voltage Test
For accurate voltage readings, batteries must remain idle (no charging, no discharging) for at least 8 hours, preferably 24 hrs.
- Disconnect all loads from the batteries.
- Test specific gravity if possible. The OCV of the tested cell will be the specific gravity reading + .84
- Example 1.22 s.g. + .84 = 2.06V 3. Measure the voltage using a DC voltmeter.
- Check the state of charge with the Table below.
- Charge the battery if it registers 0% to 75 % charged.
After the charge, if the battery registers below the Temperature Compensated values illustrated in “How can you tell if a battery is fully charged” or “How can I measure my battery's State of Charge,” the following conditions may exist:
- The battery was left in a state of discharge for too long.
- The battery has a bad cell.
Batteries in these conditions should be taken to a specialist for further evaluation or retired from service.
Load Testing
- Use this same procedure for VRLA DRY CELL batteries and flooded batteries:
- Recharge if the open circuit voltage is below 75%.
- If you have an adjustable load tester, set the load at 3 to 3.5 times the 20-hour rate.
- Apply the load for 15 seconds. The voltage should stabilize above 9.6 volts while on load.
- If the battery has a CCA rating, you can apply a load equal to ½ the rating for 15 seconds. The voltage should stabilize above 9.6 volts while on load.
- To apply a more determined test, you may apply a load equal to 100% of the rated CCA or 5 to 6 times the 20-hour rate for 30 seconds. The voltage should stabilize above 7.2 volts while on load.
- If below 9.6 volts (7.2 volts for the 100% CCA test), recharge and repeat the test. If below 9.6 volts (7.2 volts for the 100% CCA test) again, replace the battery.